EC-Light is a complete LONWORKS lighting control system, designed to meet the requirements of any commercial or industrial application. EC-Light allows energy efficient lighting applications including general area or accent lighting as well as lighting schemes, sequences and relay group management. EC-Light is a networkable lighting system which interfaces with the LONWORKS network and its subsystems (such as HVAC), providing an integrated energy management system.
|
| The EC-Light devices are easily configured using an EC-Configure LNS based plug-in, with a network management tool such as Distech Controls’ Lonwatcher. |
| |
 |
Mounted in steel enclosures ready for mounting within an electrical room, the EC-Light Panels are available in sizes 8, 16, 32 and 64 relays. The Panels come standard with input controller, heavy-duty relays, output controllers, 120/277/347 Volt transformer, and movable protection plate between high and low voltage sections. For additional functionality, an EC-Light-Scheduler or EC-Light-Display can be mounted onto the panels.
Each input controller allows for 8 low-voltage switches, which share a common low-voltage wiring run thus eliminating expensive multiple home runs or 16 dry contacts. Furthermore, the input controller is compatible with low-voltage switches, and sensors, such as occupancy or photocell sensors. The output controls a selection
|
|
of two-wire relays, allowing for 16 outputs per controller. The HID, two-wire relays offer true feedback and manual override, are latched and have a life cycle of 50,000 cycles.
Relays can be organized into groups allowing the following parameters to be set for additional energy efficiency:
| • |
Warning period through flickering of lights to announce system will turn off, giving time for local users to bypass the system if necessary or to leave the building. |
| • |
Maintenance/security crew bypass of lighting system for a specific amount of time. |
| • |
Hold time through switch or motion detection, allowing the user to initiate the system for a specified time period. |
| • |
Time delay override, allowing a user to override the lighting system for a specific amount of time. |
|
| |
|
 |
|
|
- Multi-function LCD device allowing you to manage systems without requiring a supervising station
- Display and interface with up to 250 network variables • Interface with any LONWORKS device, using SNVTs or UNVTs, integrating both lighting and HVAC
- Integrated scheduler: manage up to 16 independent schedules
- Configurable using EC-Configure LNS plug-in
|
| |
|
|
|

Factory Authorized Field Office
|
| |
 |
|
 |
|
-
For storing and managing the scheduled events required for your lighting control system
-
Up to 16 independent schedules
-
Astronomical clock to calculate the sunset and sunrise of any location on the planet.
-
Seven day templates per scheduler, 6 configurable events per day, per schedule and 4 holiday templates per schedule
-
EC-Light Scheduler can be used on itself or mounted within an EC-Light Panel
-
Configurable using EC-Configure LNS plug-in
|
| |
|
|
|
| |
|
|